Picture the annual alarm test at a busy warehouse. The alarm sounds, the fire shutter at the end of the dock starts to come down, and then it stops halfway. Maybe a pallet is in the way. Maybe a guide has bent. Either way, the opening that was meant to hold back a fire is now a gap. Fire door maintenance exists to catch exactly that kind of failure.
Finding that on test day is far better than finding it in a real fire. The building warrant of fitness (BWoF) system, set out in MBIE’s guidance on managing your BWoF, is built around the same idea. But it only works if someone looks after those doors, shutters and curtains all year, not just in the week before the paperwork is due.
Your building’s compliance schedule sets how often fire doors are checked, so there is no single national interval. MBIE notes the frequency varies by system and might be weekly, monthly, six-monthly or annual. The owner issues a building warrant of fitness every 12 months, backed by an annual Form 12A certificate from an independent qualified person.
Why fire doors, shutters and curtains need ongoing checks
A fire door is more than a rated leaf. It is a complete tested doorset: the leaf, frame, seals, hardware, installation and documentation. The rating only holds while all of those parts are doing their job. For background on how ratings are written and read, see our guide to NZ fire ratings for doors.Â
Daily use wears that system down. Closers drift, trolleys damage seals, forklift clip frames, and doors get wedged open on busy shift. MBIE passive fire guidance lists doors secured open, self-closers that do not close the door onto the latch, and damaged or missing smoke seals among the common problems when checks are skipped.
Shutters and curtains have a different problem. They spend most of their lives doing nothing, then have to work perfectly once. A shutter that has not been dropped since commissioning is a shutter nobody can vouch for.
How the BWoF and compliance schedule work
A building warrant of fitness (BWoF) is the building owner’s manual statement that the specified systems on the building’s compliance schedule have been inspected, maintained and reported on as required over the previous 12 months.
Under the Building Act 2004, a building with certain safety systems, known as specified systems, needs a compliance schedule and an annual BWoF. Single residential buildings are generally excluded. The council issues the compliance schedule, usually with the code compliance certificate. It lists the building’s specified systems, the performance standards they must meet, and the inspection, maintenance and reporting procedures that keep them working.
The owner is responsible for making sure this happens. Every 12 months the owner signs, issues and displays the BWoF to confirm the schedule has been followed. An independent qualified person (IQP), approved by the council to inspect particular specified systems, inspects and certifies those systems. Independent means they have no financial interest in the building. For each system, an IQP issues a Form 12A, which is attached to the BWoF.
Councils do audit this. New Plymouth District Council, for example, checks that the current BWoF is on display, reviews the inspection records and expects the last two years of records to be kept on site. Its inspectors also note obvious problems, such as fire doors that do not self-close properly or are wedged open.
Which specified systems involve your doors
The national list of specified systems is long, but only a few items matter for doors, shutters and curtains. Automatic or electromagnetic doors and windows that close when the fire alarm activates are on it. So are smoke control systems. Fire separations and smoke separations can be on it too, but only where they form part of the building’s means of escape from fire, and that escape route also contains certain other specified systems, such as sprinklers, fire alarms, emergency lighting or smoke control. MBIE lists hinged doors and roller shutters among the elements that can form part of a fire separation.
| System | What it covers | When it applies to your doors |
|---|---|---|
| SS 3 | Automatic or electromagnetic doors and windows | Where they close when the fire alarm activates |
| SS 13 | Smoke control systems | Where smoke control is part of the building’s design |
| SS 15 | Fire separations and smoke separations, among other features | Only where they form part of the means of escape from fire, and that escape route also contains certain other specified systems |
So not every fire door, shutter or curtain is on a compliance schedule. Which of yours are depends on how the building was designed and consented, so check your own schedule rather than assuming. If a fire shutter or smoke curtain was added after the original consent, confirm it is actually on the schedule.
Fire door maintenance: who checks what, and how often
The compliance schedule sets how often each check happens and who does it. MBIE says inspection frequency varies by system, from weekly to annual. It’s example schedule gives a daily check by the occupier that doors are not secured open and close onto the latch, and a monthly check that doors are undamaged, seals are intact and self-closing works. The guidance was last updated in 2016, so treat it as an example. Your own schedule is the rule.
What does not vary is the paperwork. Keep the current compliance schedule in the location named on the compliance schedule and the BWoF, so an auditor can find it. MBIE says owners must keep all records of inspection, maintenance and repairs for at least two years after they are issued, and annual written reports stay with the compliance schedule. If a check is missed or a defect is found, the record should show what was done, when, and by whom.
The annual BWoF cycle at a glance
- Council issues the compliance schedule. It lists your specified systems and the inspection, maintenance and reporting procedures.
- Routine checks happen all year. Your schedule says who does each check and how often.
- The IQP inspects and certifies. The independent qualified person issues a Form 12A for each system they inspect.
- The owner signs, issues and displays the BWoF every 12 months, with the Form 12A certificates attached.
- Records are kept. Inspection, maintenance and repair records are kept for at least two years.
Check your own compliance schedule for the exact frequencies that apply to your site.
What goes wrong on fire doors, shutters and curtains
Hinged and sliding fire doors
The first question is whether it closes fully and latches from any open position, every time. Next come the seals and edges. Is the leaf or frame damaged? Are the seals intact? Has any hardware been swapped for something that was not part of the tested doorset? Hardware or seals that were not part of the tested doorset can change how the door performs, so have a technician who knows the tested configuration look at any repair.
Changes around the door matter too. A new cable run or pipe through a fire-rated wall is a hole in the seperation. MBIE lists penetrations that are not properly sealed as a common problem and says retrofit work needs careful management. Alterations to a doorset or fire-rated wall, other than maintenance or repair, need building consent.
Fire shutter inspection: the alarm drop
A fire shutter inspection starts with the alarm drop. Does it release when the alarm sounds, travel all the way down and close fully with nothing underneath? Does it rest afterwards?
What a good fire shutter drop test looks like
- It releases when the alarm sounds.
- It travels all the way down.
- It closes fully with nothing underneath.
- It resets after the test.
- The result, and any fix, is recorded.
A shutter that stops short or does not reset needs fixing before the next audit, not at it.
MBIE’s example schedule for fire roller shutters, from the same 2016 guidance, shows a monthly inspection, quarterly maintenance of the operating mechanism and running gear, and a check that the shutter closes when the fusible link is released. It is an example, not a rule, so work from your own schedule.
Smoke curtain maintenance: test the whole chain
Smoke curtain maintenance has to cover a chain of parts: a trigger, a control, a power supply and the curtain itself. The useful test is the whole chain, from alarm signal to fully deployed. If any one link is untested, the system is unproven. Our explainer on how a fire-rated curtain works covers how it is triggered and deploys.
Why the repair matters more than the report
An inspection that finds a defect is only half the job. The defect still needs fixing by someone who knows how the product is built and what the approved repair is. If your fire doors and shutters came from than one supplier, that can mean chasing several different people.
Ulti installs and services fire-rated doors, roller shutters and curtains. Ulti Care is Ulti’s preventative maintenance service for doors, dock systems and access solutions, and it covers all makes and models. To see what a visit involves, read what happens during a preventative maintenance visit. There are three tiers of Ulti Care, summarised below. Support needs no contract. Protect and Shield run on 12, 24, or 36-month agreements, which the Ulti Care FAQs explain.
| Tier | What you get |
|---|---|
| Support | On-demand, no contract. A report on equipment condition after each service, minor issues fixed on the visit, and bigger jobs quoted. |
| Protect | Everything in Support, plus proactive scheduling and locked-in pricing. |
| Shield | Everything in Protect, plus 24/7 technical support, call-out charges included during normal working hours, and a dedicated account manager with quarterly reviews. |
Ulti Care handles servicing and repairs. Your IQP is still the independent inspector who signs off the systems on your compliance schedule.
FAQ
How often do fire doors need to be inspected in NZ? Your building’s compliance schedule sets the frequency, not one national number. The owner issues a BWoF every 12 months, and the IQP provides an annual certificate (Form 12A) for each system they inspect. MBIE notes that some systems are checked as often as weekly, and your schedule says which ones and by whom. See MBIE’s guide to managing your BWoF.
What is the difference between a compliance and a BWoF? The compliance schedule is issued by the council and lists the building’s specified systems, their performance standards and the inspection, maintenance and reporting procedures. The BWoF is the owner’s annual statement that those procedures were followed in the last 12 months.
Who is responsible for fire door maintenance, the owner or the tenant? The building owner is responsible for the compliance schedule and the BWoF. The schedule may assign routine checks, such as making sure doors are not wedged open, to the occupier, so check your own schedule.
Who can inspect fire doors for a BWoF? An independent qualified person (IQP) approved by the council to inspect that type of specified system. Independent means no financial interest in the building. Owners and facility teams still do routine checks between IQP visits where the schedule asks for them.
What happens if a fire shutter does not close after an alarm? Treat it as a fault in a fire protection system. Tell whoever manages your compliance schedule, arrange a repair through a competent technician as quickly as you can, and keep a record of the fault and the fix. Ask your IQP whether it needs to be noted against the schedule.
Does my warehouse need a BWoF? If the building has any specified system, such as automatic doors that close on fire alarm activation, smoke control, or fire separations that form part of the means of escape, then yes. Single residential buildings are generally excluded. The simplest check is to look at the compliance schedule that came with your code compliant certificate.
What records should I keep? Keep the current compliance schedule, the inspection and maintenance records for each specified system, and the IQP certificates. MBIE says owners must keep records for at least two years, after they are issued, and councils such as New Plymouth check them on site at audit.
Book a fire door and shutter check
If you are not sure what your doors, shutters and curtains would do on the day of the alarm test, find out before the auditor does. Book a free consultation with Ulti Group and see what a service plan could look like for your site in the 3 tiers of Ulti Care. You can also browse our fire-rated doors and smoke curtains, including the insulated fire-rated roller shutter.